BHVAC
Detailed Information
ApplicationReference to standard
EN60079-0: 2006, EN 60079-1 :
2007,EN60079-7:2007, EN60079-11:2007, EN60079- 14:2007,
EN13463-1:2001,EN13463-5:2003, GB3836.1-2000, GB3836.2-2000, GB3836 3-2000,GB3836.4-2000,
GB3836.15-2000.
Environment conditions of normal operation
1 It is used in which elevation is less than 2000m the range of atmospheric pressure is 80kPa~ 110kPa.
2 Ambient temperature: -30"C~+60*C.
3 Ambient relative humidity is not more than 90% (+25C )
4 It is used in the places, where is classified as Zone 1 or Zone 2, contained the explosive gas mixture, Group II
A, Group II B, Group II C, temperature group T1 ~ T3.
DATA SHEET & PERFORMACE |
|||
BHVAC-8(Cooling capacity:6~12KW) |
|||
No. |
Items |
KNEX Specifications |
Note |
1 |
Name |
Explosion-proof heating ventilation air |
No heating fuction |
2 |
Model |
BHVAC-12 |
|
3 |
Type |
Packaged |
|
4 |
Area Class |
Zone 2, Gas Gr. IIC, T3 |
|
5 |
E-mark |
II2G ExdeibIICT3 |
|
6 |
Certificate |
ATEX |
|
7 |
Compliance |
EN60079 |
|
8 |
Ambient temperature |
+21℃ bis +52℃ |
The unit is able to work in operation range. |
9 |
AC casing |
S304 Stainless steel |
|
Cooling system |
|||
1 |
Cooling capacity (nominal) |
6~12KW |
|
2 |
Refrigeration circuits |
1*100% |
|
3 |
Refrigerant |
R134a |
|
4 |
Compressor |
Hermetic scroll |
|
5 |
Protection |
Ex-d |
|
6 |
Compressor motor |
Internally Integrated |
|
7 |
Evaporator material |
Cu tube / Al fins |
Provide maxium transfer |
8 |
Condenser material |
Cu tube / Al fins |
Provide maxium transfer |
Ventilation fan |
|||
1 |
Fan arrangement |
1*100% |
|
2 |
Contruction |
Non sparking |
|
3 |
Drive Type |
Direct |
|
4 |
Protection |
Ex-d |
|
Condenser fan |
|||
1 |
Fan arrangement |
1*100% |
|
2 |
Contruction |
Non sparking |
|
3 |
Drive Type |
Direct |
|
4 |
Protection |
Ex-d |
|
Control panel |
|||
1 |
Material |
Aluminum |
|
2 |
Protection |
Ex-d |
|
3 |
Dimension |
246*230*90(H)mm |
|
4 |
Install location |
Inside house |
|
5 |
Weight |
8kg |
|
Dimension see drawing |